Equation 4-1:
U = 1/[Rs + (ER)]
Where:
Rs = The cumulative R-value of the wall components along the path of heat transfer, excluding the cavity insulation and steel studs.
ER = The effective R-value of the cavity insulation with steel studs as specified in Table C402.1.4.2.
When the total area of penetrations from through-wall mechanical equipment or equipment listed in Table C403.3.2(4) exceeds 1 percent of the opaque above-grade wall area, the mechanical equipment penetration area shall be calculated as a separate wall assembly with a default U-factor of 0.5. Mechanical system ducts and louvers, including those for supply, exhaust and relief, and for condenser air intake and outlet, are not considered to be mechanical equipment for the purposes of this section.
EXCEPTION: | Where mechanical equipment has been tested in accordance with approved testing standards, the mechanical equipment penetration area is permitted to be calculated as a separate wall assembly using the U-factor determined by such test. |
Wash. Admin. Code § 51-11C-40214
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. 13-04-056, § 51-11C-40214, filed 2/1/13, effective 7/1/13.