The vertical clearance for overhead power and communication lines above the highway and the lateral and vertical clearance from bridges shall conform with the National Electrical Safety Code and/or with the clearances as shown below, whichever is greater.
TYPE OF UTILITY LINE | LINES CROSSING ROADWAYS | LONGI- TUDINAL |
Communications and Cable Television Communications and/or Cable Television joint usage with electrical ELECTRICAL 0 - 750 volts 751 - 15,000 volts 15,001 - 50,000 volts 50,001 volts and over | 24' 20' 24' 30' 32' 34' | 20' 20' 24' 27' 32' 32' |
Wash. Admin. Code § 468-34-290
Statutory Authority: Chapter 47.44 RCW. 89-05-022 (Order 119), § 468-34-290, filed 2/10/89. Statutory Authority: 1977 ex.s. c 151. 79-01-033 (DOT Order 10 and Comm. Order 1, Resolution No. 13), § 468-34-290, filed 12/20/78. Formerly WAC 252-04-255.