Wash. Admin. Code § 388-107-0980

Current through Register Vol. 24-12, June 15, 2024
Section 388-107-0980 - Mechanical-Heating systems

The facility must ensure:

(1) The heating system is capable of maintaining a temperature of seventy-five degrees Fahrenheit for areas occupied by residents and seventy degrees Fahrenheit for non-resident areas.
(2) Resident rooms must have individual temperature control which may be covered, locked, or placed in an inconspicuous place.
(3) Electric resistant wall heat units and portable space heaters are prohibited.
(4) The heating system must be connected to an alternate source of power, or an alternate source of heating must be provided to maintain the temperature in resident rooms or in a room to which all residents can be moved.

Wash. Admin. Code § 388-107-0980

Adopted by WSR 14-19-071, Filed 9/12/2014, effective 10/13/2014