Section 296-96-05020 - Hoistway enclosure

Generally, local codes and ordinances govern hoistway enclosure construction. When not in conflict with a local code requirement, the enclosure shall:

(1) Be built to a height of 2133.6 mm (84 in.) above each floor, landing and adjacent stairway tread;
(2) Extend (adjacent to the counterweights) the full height of the floor and 203.2 mm (8 in.) beyond the counterweight raceway;
(3) Be constructed of either solid material or material with openings that will reject a 50.8 mm (2 in.) diameter ball;
(4) Be supported and braced so that it does not deflect more than 25.4 mm (1 in.) when subjected to a force of 100 lbs. applied perpendicular at any point;
(5) A full height hoistway enclosure is required only on the side(s) of the material lift for which the car is not equipped with a gate or enclosure.