Table H-24
TABLE OF DISTANCES FOR STORAGE OF LOW EXPLOSIVES
Pounds | From inhabited building distance (feet) | From public railroad and highway distance (feet) | From above ground magazine (feet) | |
Over | Not Over | |||
0 | 1,000 | 75 | 75 | 50 |
1,000 | 5,000 | 115 | 115 | 75 |
5,000 | 10,000 | 150 | 150 | 100 |
10,000 | 20,000 | 190 | 190 | 125 |
20,000 | 30,000 | 215 | 215 | 145 |
30,000 | 40,000 | 235 | 235 | 155 |
40,000 | 50,000 | 250 | 250 | 165 |
50,000 | 60,000 | 260 | 260 | 175 |
60,000 | 70,000 | 270 | 270 | 185 |
70,000 | 80,000 | 280 | 280 | 190 |
80,000 | 90,000 | 295 | 295 | 195 |
90,000 | 100,000 | 300 | 300 | 200 |
100,000 | 200,000 | 375 | 375 | 250 |
200,000 | 300,000 | 450 | 450 | 300 |
Wash. Admin. Code § 296-52-69125
Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. 03-06-073, § 296-52-69125, filed 3/4/03, effective 8/1/03. Statutory Authority: RCW 49.17.010,[49.17].040 , and [49.17].050. 02-03-125, § 296-52-69125, filed 1/23/02, effective 3/1/02.