TABLE H-5
Type of tank | Protection | Minimum distance in feet from property line which may be built upon, including the opposite side of a public way. | Minimum distance in feet from nearest side of any public way or from nearest important building and shall be not less than 5 feet. |
Floating roof _______ | Protection for exposures. | 1/2 times diameter of tank but need not exceed 90 ft. | 1/6 times diameter of tank but need not exceed 30 ft. |
None _______ | Diameter of tank but need not exceed 175 ft. | 1/6 times diameter of tank but need not exceed 30 ft. | |
Vertical with weak roof to shell seam | Approved foam or inerting system on the tank. | 1/2 times diameter of tank but need not exceed 90 ft. and shall not be less than 5 ft. | 1/6 times diameter of tank but need not exceed 30 ft. |
Protection for exposures. | Diameter of tank but need not exceed 175 ft. | 1/3 times diameter of tank but need not exceed 60 ft. | |
None | 2 times diameter of tank but need not exceed 350 ft. | 1/3 times diameter of tank but need not exceed 60 ft. | |
Horizontal and vertical, with emergency relief venting to limit pressures to 2.5 p.s.i.g. | Approved inerting system on the tank or approved foam system on vertical tanks. | 1/2 times Table H-9 but shall not be less than 5 ft. | 1/2 times Table H-9. |
Protection for exposures. | Table H-9 _______ | Table H -9 | |
None _______ | 2 times table _______ | Table H -9 |
TABLE H-6
Type of tank | Protection | Minimum distance in feet from property line which may be built upon, including the opposite side of a public way. | Minimum distance in feet from nearest side of any public way or from nearest important building. |
Any type | - Protection for exposures. | 1 1/2 times Table H-9 but shall not be less than 25 ft. | 1 1/2 times Table H-9 but shall not be less than 25 ft. |
None _______ | 3 times Table H-9 but shall not be less than 50 ft. | 1 1/2 times Table H-9 but shall not be less than 25 ft. |
TABLE H-7
Type of tank | Protection | Minimum distance in feet from property line which may be built upon, including the opposite side of a public way. | Minimum distance in feet from nearest side of any public way or from nearest important building. |
Floating roof _______ | Protection for exposures. | Diameter of tank but need not exceed 175 ft. | 1/3 times diameter of tank but need not exceed 60 ft. |
None _______ | 2 times diameter of tank but need not exceed 350 ft. | 1/3 times diameter of tank but need not exceed 60 ft. | |
Fixed roof _______ | Approved foam or inerting system. | Diameter of tank but need not exceed 175 ft. | 1/3 times diameter of tank but need not exceed 60 ft. |
Protection for exposures. | 2 times diameter of tank but need not exceed 350 ft. | 2/3 times diameter of tank but need not exceed 120 ft. | |
None _______ | 4 times diameter of tank but need not exceed 350 ft. | 2/3 times diameter of tank but need not exceed 120 ft. |
TABLE H-8
Type of tank | Protection | Minimum distance in feet from property line which may be built upon, including the opposite side of a public way. | Minimum distance in feet from nearest side of any public way or from nearest important building. |
Floating roof _______ | Protection for exposures. | Diameter of tank but need not exceed 175 ft. | 1/3 times diameter of tank but need not exceed 60 ft. |
None _______ | 2 times diameter of tank but need not exceed 350 ft. | 1/3 times diameter of tank but need not exceed 60 ft. | |
Fixed roof _______ | Approved foam or inerting system. | Diameter of tank but need not exceed 175 ft. | 1/3 times diameter of tank but need not exceed 60 ft. |
Protection for exposures. | 2 times diameter of tank but need not exceed 350 ft. | 2/3 times diameter of tank but need not exceed 120 ft. | |
None _______ | 4 times diameter of tank but need not exceed 350 ft. | 2/3 times diameter of tank but need not exceed 120 ft. |
TABLE H-9
Capacity tank gallons | Minimum distance in feet from property line which may be built upon, including the opposite side of a public way. | Minimum distance in feet from nearest side of any public way or from nearest important building | |
275 | or less | _______5 | 5 |
276 | to | 750 _______ 10 | 5 |
751 | to | 12,000 _______ 15 | 5 |
12,001 | to | 30,000 _______ 20 | 5 |
30,001 | to | 50,000 _______ 30 | 10 |
50,001 | to | 100,000 _______50 | 15 |
100,001 | to | 500,000 _______ 80 | 25 |
500,001 | to | 1,000,000 _______ 100 | 35 |
1,000,001 | to | 2,000,000 _______ 135 | 45 |
2,000,001 | to | 3,000,000 _______ 165 | 55 |
3,000,001 | or more | _______175 | 60 |
Exemption: | Tanks of 3,000 bbls. (barrels) capacity or less containing crude petroleum in crude-producing areas; and, outside aboveground atmospheric tanks under 1,000 gallons capacity containing other than Category 1 flammable liquids may have open vents. (See (2)(f)(ii) of this section.) |
TABLE 10
WETTED AREA VERSUS CUBIC FEET FREE AIR PER HOUR
(14.7 psia and 60°F)
Square feet | CFH | Square feet | CFH | Square feet | CFH |
20 | 21,100 | 200 | 211,000 | 1,000 | 524,000 |
30 | 31,600 | 250 | 239,000 | 1,200 | 557,000 |
40 | 42,100 | 300 | 265,000 | 1,400 | 587,000 |
50 | 52,700 | 350 | 288,000 | 1,600 | 614,000 |
60 | 63,200 | 400 | 312,000 | 1,800 | 639,000 |
70 | 73,700 | 500 | 354,000 | 2,000 | 662,000 |
80 | 84,200 | 600 | 392,000 | 2,400 | 704,000 |
90 | 94,800 | 700 | 428,000 | 2,800 | 742,000 |
100 | 105,000 | 800 | 462,000 | and | |
120 | 126,000 | 900 | 493,000 | over | |
140 | 147,000 | 1,000 | 524,000 | ||
160 | 168,000 | ||||
180 | 190,000 | ||||
200 | 211,000 |
CFH = 1,107A0.82
Where:
CFH = Venting requirement, in cubic feet of free air per hour.
A = Exposed wetted surface, in square feet.
Note: | The foregoing formula is based on Q = 21,000A0.82. |
Cubic feet of free air per hour = V
V = Cubic feet of free air per hour from Table H-10.
L = Latent heat of vaporization of specific liquid in B.t.u. per pound.
M = Molecular weight of specific liquids.
0.5 for drainage in accordance with (2)(g)(ii) of this section for tanks over 200 square feet of wetted area.
0.3 for approved water spray.
0.3 for approved insulation.
0.15 for approved water spray with approved insulation.
TABLE H-11
VENT LINE DIAMETERS
Maximum flow GPM | Pipe length* | ||
50 feet | 100 feet | 200 feet | |
Inches | Inches | Inches | |
100 _________ | 1 1/4 | 1 1/4 | 1 1/4 |
200 _________ | 1 1/4 | 1 1/4 | 1 1/4 |
300 _________ | 1 1/4 | 1 1/4 | 1 1/2 |
400 _________ | 1 1/4 | 1 1/2 | 2 |
500 _________ | 1 1/2 | 1 1/2 | 2 |
600 _________ | 1 1/2 | 2 | 2 |
700 _________ | 2 | 2 | 2 |
800 _________ | 2 | 2 | 3 |
900 _________ | 2 | 2 | 3 |
1,000 _________ | 2 | 2 | 3 |
* Vent lines of 50 ft., 100 ft., and 200 ft. of pipe plus 7 ells.
Wash. Admin. Code § 296-24-33005
Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 06-05-027, § 296-24-33005, filed 2/7/06, effective 4/1/06. Statutory Authority: Chapter 49.17 RCW. 94-15-096 (Order 94-07), § 296-24-33005, filed 7/20/94, effective 9/20/94; 88-23-054 (Order 88-25), § 296-24-33005, filed 11/14/88; Order 76-6, § 296-24-33005, filed 3/1/76; Order 73-5, § 296-24-33005, filed 5/9/73 and Order 73-4, § 296-24-33005, filed 5/7/73.