Table I-1 Working Clearances
Nominal Voltage to Ground | Minimum Clear Distance for Conditions 1 | ||
(a) | (b) | (c) | |
Feet 2 | Feet 2 | Feet 2 | |
0-150............ | 3 | 3 | 3 |
151-600........... | 3 | 3 1/2 | 4 |
1 | Conditions (a), (b), and (c) are as follows: (a) Exposed live parts on one side and no live or grounded parts on the other side of the working space, or exposed live parts on both sides effectively guarded by insulating material. Insulated wire or insulated busbars operating at not over 300 volts are not considered live parts. (b) Exposed live parts on one side and grounded parts on the other side. (c) Exposed live parts on both sides of the workspace not guarded provided in condition (a) with the operator between. |
2 | Note: For International System of Units (S1): One foot = 0.3048m. |
Table I-2 Minimum Depth of Clear Working Space in Front of Electric Equipment
Nominal Voltage to Ground | Minimum Clear Distance for Conditions 1 | ||
(a) | (b) | (c) | |
Feet 2 | Feet 2 | Feet 2 | |
601 to 2,500............... | 3 | 4 | 5 |
2,501 to 9,000.............. | 4 | 5 | 6 |
9,001 to 25,000............. | 5 | 6 | 9 |
25,001 to 75kV............. | 6 | 8 | 10 |
Above 75kV............... | 8 | 10 | 12 |
1 | Conditions (a), (b), and (c) are as follows: (a) Exposed live parts on one side and no live or grounded parts on the other side of the working space, or exposed live parts on both sides effectively guarded by insulating materials. Insulated wire or insulated busbars operating at not over 300 volts are not considered live parts. (b) Exposed live parts on one side and grounded parts on the other side. Walls constructed of concrete, brick, or the tile are considered to be grounded surfaces. (c) Exposed live parts on both sides of the workspace (not guarded as provided in Condition (a)) with the operator between. |
2 | Note: For S1 units: One foot = 0.3048m. |
Table I-3
Elevation of Unguarded
Energized Parts Above Working Space
Nominal Voltage to Between Phases | Minimum Elevation |
601 to 7,500................. | 8 feet 6 inches1 |
7,501 to 35,000................ | 9 feet |
Over 35kV................... | 9 feet + 0.37 inches per kV above 35kV |
1 | Note: For S1 units: One inch = 25.4mm, one foot = 0.3048m. |
Wash. Admin. Code § 296-155-444
Statutory Authority: Chapter 49.17 RCW. 93-19-142 (Order 93-04), § 296-155-444, filed 9/22/93, effective 11/1/93; 92-23-017 (Order 92-13), § 296-155-444, filed 11/10/92, effective 12/18/92; 88-11-021 (Order 88-04), § 296-155-444, filed 5/11/88.