Note: | The provisions of this subdivision do not apply to portable heaters under 7,500 BTU per hour input when used with containers having a maximum water capacity of 2 1/2 pounds. |
Quantity of LP-gas store | TABLE D-3 d: | Distance (feet) |
500 lbs. or less | 0 | |
501 to 6,000 lbs. | 10 | |
6,001 to 10,000 lbs. | 20 | |
Over 10,000 lbs. | 25 |
Note: | For additional requirements relating to portable fire extinguishers see WAC 296-800-300. |
Wash. Admin. Code § 296-155-275
Statutory Authority: RCW 49.17.010, [49.17].040, and[49.17].050 . 01-17-033, § 296-155-275, filed 8/8/01, effective 9/1/01. Statutory Authority: RCW 49.17.040 and 49.17.050. 86-03-074 (Order 86-14), § 296-155-275, filed 1/21/86; Order 76-29, § 296-155-275, filed 9/30/76; Order 74-26, § 296-155-275, filed 5/7/74, effective 6/6/74.