Note: | One 55-gallon open drum of water with two fire pails may be substituted for a fire extinguisher having a 2A rating. |
Note: | For additional requirements relating to portable fire extinguishers see WAC 296-800-300. |
Note: | One hundred feet, or less, of 1-1/2 inch hose, with a nozzle capable of discharging water at 25 gallons or more per minute, may be substituted for a fire extinguisher rated not more than 2A in the designated area provided that the hose line can reach all points in the area. |
Note: | Modification of sprinkler systems to permit alterations or additional demolition should be expedited so that the automatic protection may be returned to service as quickly as possible. Sprinkler control valves must be checked daily at close of work to ascertain that the protection is in service. |
Wash. Admin. Code § 296-155-260
Statutory Authority: RCW 49.17.010, [49.17].040, and[49.17].050 . 01-23-060, § 296-155-260, filed 11/20/01, effective 12/1/01; 01-11-038, § 296-155-260, filed 5/9/01, effective 9/1/01. Statutory Authority: Chapter 49.17 RCW. 94-15-096 (Order 94-07), § 296-155-260, filed 7/20/94, effective 9/20/94. Statutory Authority: RCW 49.17.040 and 49.17.050. 86-03-074 (Order 86-14), § 296-155-260, filed 1/21/86; Order 76-6, § 296-155-260, filed 3/1/76; Order 74-26, § 296-155-260, filed 5/7/74, effective 6/6/74.