The installation of all manufactured homes shall comply with the requirements of this section.
* A manufactured home is installed over a basement and the manufacturer's instructions do not address this application;
* A manufactured home is installed on a site where the specific soil bearing capacity is not addressed in the manufacturer's instructions.
If the manufacturer's skirting and access instructions are not specific, skirting, ventilation and access shall be installed as follows:
* Must be made of materials suitable for ground contact.
* Metal fasteners must be made of galvanized, stainless steel or other corrosion-resistant material.
* Ferrous metal members in contact with the earth, except those made of galvanized or stainless steel, must be coated with an asphaltic emulsion.
* Must not trap water between the skirting and siding or trim.
* Must be recessed behind the siding or trim.
For homes sited in a flood plain, contact the local jurisdiction regarding proper skirting ventilation. Except for those manufactured homes sited in a flood plain, all skirting and vent openings must:
* Be covered with corrosion-resistant wire mesh to prevent the entrance of rodents. The size of the mesh opening cannot exceed 1/4 inch.
* Have a net area of not less than one square foot for each one hundred fifty square feet of under floor area.
* Be located as close to corners and as high as practical and provide cross ventilation on at least two opposite sides.
* The under floor area of a manufactured home must have a finished opening at least eighteen inches by twenty-four inches in size.
* Opening must be located so that all areas under a manufactured home are available for inspection.
* Opening must be covered. The cover must be made of material suitable for skirting or venting as required in this chapter.
Heat duct crossovers must be installed to avoid standing water and installed to prevent compression, sharp bends, and to minimize stress at the connections. In all cases, the duct must be supported at least one inch off the ground (exception to the Model Manufactured Home Installation Standards 24 C.F.R. Part 3285).
Wash. Admin. Code § 296-150I-0310
Statutory Authority: Chapter 43.22A RCW and 2009 c 464 [564]. 10-06-043, § 296-150I-0310, filed 2/23/10, effective 4/1/10. Statutory Authority: Chapter 43.22A RCW and 2007 c 432. 08-12-040, § 296-150I-0310, filed 5/30/08, effective 6/30/08.