Wash. Admin. Code § 246-335-748

Current through Register Vol. 24-23, December 1, 2024
Section 246-335-748 - Plumbing

An applicant must design and install plumbing, including:

(1) Backflow prevention. Devices on plumbing fixtures, equipment, facilities, buildings, premises, or areas which may cause actual or potential cross-connections of systems in order to prevent the backflow of water or other liquids, gases, mixtures, or substances into a water distribution system or other fixtures, equipment, facilities, buildings, or areas;
(2) Trap primers in floor drains and stand pipes subject to infrequent use;
(3) Wrist, knee or foot faucet controls or equivalent and gooseneck spouts on handwash sinks;
(4) Insulation on:
(a) Hot water piping systems;
(b) Cold water and drainage piping; and
(c) Piping exposed to outside temperatures.
(5) Equipment to deliver hot water at point of use as follows:
(a) 120°F or less for handwash sinks and bathing fixtures;
(b) 160°F or more for laundry washers;
(c) 120°F or more for laundry washers using chemical sanitation.

Wash. Admin. Code § 246-335-748

Adopted by WSR 18-06-093, Filed 3/6/2018, effective 4/6/2018