Wash. Admin. Code § 246-322-140

Current through Register Vol. 24-23, December 1, 2024
Section 246-322-140 - Patient living areas

The licensee shall:

(1) Provide patient sleeping rooms with:
(a) A minimum of eighty square feet of useable floor space in a single bedroom;
(b) A minimum of seventy square feet of useable floor space per bed in a multipatient room;
(c) A minimum ceiling height of seven feet six inches over the required floor area;
(d) A maximum capacity of four patients;
(e) A floor elevation no lower than three feet six inches below grade, with grade extending horizontally ten or more feet from the building;
(f) A clear window area on an outside wall equal to or greater than one-tenth the floor area with a minimum of ten square feet;
(g) Only security or maximum security windows;
(h) Direct access to and from a corridor, common-use activity room, or other common-use area;
(i) Sufficient room furnishings maintained in safe and clean condition including:
(i) A bed for each patient at least thirty-six inches wide or appropriate to the special needs and size of the patient;
(ii) A cleanable, firm mattress; and
(iii) A cleanable or disposable pillow; and
(j) At least three feet between beds, and adequate space between furnishings to allow easy entrance, exit, and traffic flow within the room;
(k) A means to assure patient privacy when appropriate;
(2) Provide, in addition to the requirements in subsection (1) of this section, when security rooms are used:
(a) Security or maximum security windows appropriate to the area and program;
(b) Furnishings, equipment and design for maximum safety and security;
(c) Shielded and tamper-resistant lighting fixtures and electrical outlets;
(d) A door lockable from the outside; and
(e) Provisions for authorized staff to observe occupants;
(3) Provide an enclosed space within the patient sleeping room, or nearby, suitable for each patient to hang garments, and store clothing and personal belongings;
(4) Provide secure storage for each patient's valuables in the patient sleeping room or conveniently available elsewhere in the hospital;
(5) Provide a dining area for patients in a community setting with furnishings appropriate for dining;
(6) Provide and maintain a safe area or areas for patient recreation and physical activity equal to or greater than twenty square feet for each licensed bed space;
(7) Provide a visiting area allowing privacy for patients and visitors;
(8) Provide a readily available telephone for patients to make and receive confidential calls; and
(9) Provide a "nonpay" telephone or equivalent communication device readily accessible on each patient occupied floor for emergency use.

Wash. Admin. Code § 246-322-140

Statutory Authority: Chapter 71.12 RCW and RCW 43.60.040. 95-22-012, § 246-322-140, filed 10/20/95, effective 11/20/95.