9 Va. Admin. Code § 25-790-960

Current through Register Vol. 40, No. 22, June 17, 2024
Section 9VAC25-790-960 - Influent and effluent sampling
A. Sampling tests and frequency. Table C lists the typical recommended minimum sampling program schedules for all sewage treatment works (STW).
B. STW effluent tests and frequency of effluent testing and frequency of other sampling for a treatment works will be provided in the VPDES permit or the VPA permit.

TABLE C. TYPICAL SAMPLING PROGRAMS FOR SEWAGE TREATMENT WORKS.
PLANT SIZE >2.01 MGD 1.0-2.0 MGD 0.101-0.999 MGD 0.401-0.1 MGD 0.0011-0.04 MGD
Flow Totalizing, Indicating & Recording Totalizing, Indicating & Recording Totalizing, Indicating & Recording Totalizing, Indicating & Recording Estimate
BOD5, TSS, TKN 24- HC 1/ Day 24- HC 5 Days/ Wk 8-HC 3 Days/ Wk 4-HC 1 Day/ Wk Grab 1/month
Total Nitrogen* Total Phosphorus* 24- HC 1/ Week 24- HC 1/ Week 8-HC 1/ 2 Weeks 4-HC 1/ Month Grab 1/month
TRC, Contact tank** Grab 1/2 Hr 4/Day at 4 Hr.Intervals 3/Day at 4 Hr.Intervals 3/Day at 4 Hr.Intervals Grab 1/Day
Fecal Coliform** Grab 1/Day 10am-4pm Grab 5 Days/Wk 10am-4pm Grab 3 Days/Wk 10am-4pm Grab 1/Week 10am-4pm Grab 1/Month 10am-4pm
pH, DO, TRC Effluent Grab 1/Day Grab 1/Day Grab 1/Day Grab 1/Day Grab 1/Day
WQS Parameters (Toxics) 1/8,24 HC or 1/month 1/8,24 HC or 1/month 1/8, 8HC or 1/month 1/8, 4HC or 1/month Grab 1/month

9 Va. Admin. Code § 25-790-960

Former 12VAC5-581-1020 derived from Virginia Register Volume 18, Issue 10, eff. February 27, 2002; amended and adopted as 9VAC25-790-960, Virginia Register Volume 20, Issue 9, eff. February 12, 2004.

Statutory Authority

§ 62.1-44.19 of the Code of Virginia.