9 Va. Admin. Code § 25-580-320

Current through Register Vol. 40, No. 22, June 17, 2024
Section 9VAC25-580-320 - Permanent closure and changes-in-service

Owners and operators must obtain a permit and the required inspections in accordance with the Virginia Uniform Statewide Building Code (§ 36-97 et seq. of the Code of Virginia).

A permit from the building official must be obtained prior to permanent tank closure or a change-in-service. No UST system shall be permanently closed or changed-in-service unless and until the system is inspected in accordance with the provisions of the Virginia Uniform Statewide Building Code (§ 36-97 et seq. of the Code of Virginia).

If such closure is in response to immediate corrective actions that necessitate timely tank removal, then the building official must be notified and the official's directions followed until a permit is issued.

In the case of state-owned facilities the Department of General Services shall function as the building official in accordance with § 36-98.1 of the Code of Virginia.

In the case of federal facilities the building official must be contacted. Owners and operators must obtain a permit and the required inspections in accordance with the provisions of the Virginia Uniform Statewide Building Code.

1. Owners and operators must within 30 days after either permanent closure or a change-in-service submit an amended UST notification form to the department.
2. The required assessment of the excavation zone under 9VAC25-580-330 must be performed after notifying the building official but before completion of the permanent closure or a change-in-service.
3. To permanently close a tank, owners and operators must empty and clean it by removing all liquids and accumulated sludges. When the owner or operator suspects that the residual sludges are hazardous in nature the Department of Environmental Quality regulations shall be followed to facilitate the proper treatment, storage, manifesting, transport, and disposal. All tanks taken out of service permanently must be removed from the ground, filled with an inert solid material, or closed in place in a manner approved by the department.
4. Continued use of an UST system to store a nonregulated substance is considered a change-in-service. Before a change-in-service, owners and operators must empty and clean the tank by removing all liquid and accumulated sludge and conduct a site assessment in accordance with 9VAC25-580-330.

NOTE: The following cleaning and closure procedures may be used to comply with this section:

a. American Petroleum Institute Recommended Practice RP 1604, Closure of Underground Petroleum Storage Tanks;
b. American Petroleum Institute Standard 2015, Safe Entry and Cleaning of Petroleum Storage Tanks, Planning and Managing Tank Entry from Decommissioning through Recommissioning;
c. American Petroleum Institute Recommended Practice 2016, Guidelines and Procedures for Entering and Cleaning Petroleum Storage Tanks;
d. American Petroleum Institute Recommended Practice RP 1631, Interior Lining and Periodic Inspection of Underground Storage Tanks, may be used as guidance for compliance with this section;
e. National Fire Protection Association Standard 326, Standard for the Safeguarding of Tanks and Containers for Entry, Cleaning, or Repair; and
f. The National Institute for Occupational Safety and Health Publication 80-106, Criteria for a Recommended Standard *** Working in Confined Space may be used as guidance for conducting safe closure procedures at some hazardous substance tanks.

9 Va. Admin. Code § 25-580-320

Derived from VR680-13-02 §7.2, eff. October 25, 1989; amended, Virginia Register Volume 20, Issue 12, eff. March 24, 2004; Amended, Virginia Register Volume 34, Issue 01, eff. 1/1/2018; Amended, Virginia Register Volume 39, Issue 5, eff. 11/23/2022.

Statutory Authority: §§ 62.1-44.15 and 62.1-44.34:9 of the Code of Virginia; 42 USC § 6901 et seq.; 40 CFR Parts 280 and 281.