Impounding structures of regulated size and not exempted shall be constructed, operated and maintained such that they perform in accordance with their design and purpose throughout the life of the project. For impounding structures, the spillway capacity shall perform at a minimum to safely pass the appropriate spillway design flood as determined in Table 1. For the purposes of utilizing Table 1, Hazard Potential Classification shall be determined in accordance with 4VAC50-20-40.
TABLE 1 Impounding Structure Regulations | |||
Applicable to all impounding structures that are 25 feet or greater in height and that create a maximum impounding capacity of 15 acre-feet or greater, and to all impounding structures that are six feet or greater in height and that create a maximum impounding capacity of 50 acre-feet or greater and is not otherwise exempt from regulation by the Code of Virginia. | |||
Hazard Potential Class of Dam | Spillway Design Flood (SDF)B for New ConstructionF | Spillway Design Flood (SDF)B for Existing Impounding StructuresF, G | Minimum Threshold for Incremental Damage Analysis |
High | PMFC | 0.9 PMPH | 100-YRD |
Significant | .50 PMF | .50 PMF | 100-YRD |
Low | 100-YRD | 100-YRD | 50-YRE |
4 Va. Admin. Code § 50-20-50
Statutory Authority: § 10.1-605 of the Code of Virginia.