TABLE R-2. Approach Distances to Exposed Energized Overhead Power Lines and Parts. | |
Voltage range (phase to phase, RMS) | Approach distance (inches) |
300 V and less | (1) |
Over 300 V, not over 750V | 12 |
Over 750 V not over 2 kV | 18 |
Over 2 kV, not over 15 kV | 24 |
Over 15 kV, not over 37 kV | 36 |
Over 37 kV, not over 87.5 kV | 42 |
Over 87.5 kV, not over 121 kV | 48 |
Over 121 kV, not over 140kV | 54 |
(1) Avoid contact.
16 Va. Admin. Code § 25-75-10