TABLE 2 Minimum Pounds of Steam Per Hour Per Square Foot of Heating Surface | ||
Fire Tube Boilers | Water Tube Boilers | |
Boiler Heating Surface: | ||
Hand fired | 5 | 6 |
Stoker fired | 7 | 8 |
Oil, gas, or pulverized fuel fired | 8 | 10 |
Waterwall Heating Surface: | ||
Hand fired | 8 | 8 |
Stoker fired | 10 | 12 |
Oil, gas, or pulverized fuel fired | 14 | 16 |
NOTES: When a boiler is fired only by a gas giving a heat value of not in excess of 200 BTU per cubic foot, the minimum safety valve or safety relief valve relieving capacity may be based on the value given for handfired boilers in Table 2. The minimum safety valve or safety relief valve relieving capacity for electric boilers shall be 3-1/2 pounds per hour per kilowatt input. For heating surface determination, see the current edition of the ASME Code, Section IV. |
16 Va. Admin. Code § 25-50-370
Statutory Authority: § 40.1-51.6 of the Code of Virginia.