13 Va. Admin. Code § 5-63-250

Current through Register Vol. 41, No. 6, November 4, 2024
Section 13VAC5-63-250 - Chapter 11 Accessibility
A. Add an exception to Section 1102.1 of the IBC to read:

Exception: Wall-mounted visible alarm notification appliances in Group I-3 occupancies shall be permitted to be a maximum of 120 inches (3048 mm) above the floor or ground, measured to the bottom of the appliance. Such appliances shall otherwise comply with all applicable requirements.

B. Change Section 1103.2.8 of the IBC to read:
1103.2.8 Raised and lowered areas in places of religious worship. Raised or lowered areas or portions of areas in places of religious worship are not required to be accessible or to be served by an accessible route, provided such areas are used primarily for the performance of religious ceremonies and are located within an accessible story or mezzanine.
C. Add Section 1103.2.15 to the IBC to read:
1103.2.15 Emergency supplemental hardware. In Group E occupancies, except Group E day care facilities, Group B educational occupancies, and public buildings, emergency supplemental hardware is not required to comply with this chapter when deployed during an active shooter or hostile threat event and provided in accordance with Section 1010.2.8.
D. Change Section 1106.2 of the IBC and replace Table 1106.2 of the IBC with Tables 1106.2(1) and 1106.2(2) to read:
1106.1 Required. Where parking is provided, accessible parking spaces shall be provided in compliance with Tables 1106.2(1) and 1106.2(2), as applicable, except as required by Sections 1106.3 through 1106.5. Where more than one parking facility is provided on a site, the number of parking spaces required to be accessible shall be calculated separately for each parking facility.

Exception: This section does not apply to parking spaces used exclusively for buses, trucks, other delivery vehicles, law-enforcement vehicles, or vehicular impound and motor pools where lots accessed by the public are provided with an accessible passenger loading zone.

Table 1106.2(1) Accessible Parking Spaces for Groups A, B, E, M, R-1, R-2, and Ia

Total Parking Spaces Provided

Required Minimum Number of Accessible Spaces

1 - 25

1

26 - 50

2

51 - 75

3

76 - 100

4

101 - 125

5

126 - 150

6

151 - 200

7

201 - 300

8

301 - 400

9

401 - 500

10

501 - 1,000

2.33% of total

1,001 and over

23, plus one for each 100, or fraction thereof, over 1,000

a. Condominium parking in Group R-2 occupancies where parking is part of the unit purchase shall be in accordance with Table 1106.2.2.

Table 1106.2(2) Accessible Parking Spaces for Groups F, S, H, R-3, R-4, and U

Total Parking Spaces Provided

Required Minimum Number of Accessible Spaces

1 - 25

1

26 - 50

2

51 - 75

3

76 - 100

4

101 - 150

5

151 - 200

6

201 - 300

7

301 - 400

8

401 - 500

9

501 - 1,000

2.0% of total

1,001 and over

20, plus one for each 100, or fraction thereof, over 1,000

E. Add Section 1106.10 to the IBC to read:
1106.10 Identification of accessible parking spaces. In addition to complying with applicable provisions of this chapter, all accessible parking spaces shall be identified by above-grade signs. A sign or symbol painted or otherwise displayed on the pavement of a parking space shall not constitute an above-grade sign. All above-grade parking space signs shall have the bottom edge of the sign no lower than four feet (1219 mm) nor higher than seven feet (2133 mm) above the parking surface. All disabled parking signs shall include the following language: PENALTY, $100-500 Fine, TOW-AWAY ZONE. Such language may be placed on a separate sign and attached below existing above-grade disabled parking signs, provided that the bottom edge of the attached sign is no lower than four feet above the parking surface.
F. Change Section 1110.2 (exceptions remain) of the IBC to read:
1110.2 Toilet and bathing facilities. Each toilet room and bathing room shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing rooms provided within the facility shall not be located on the inaccessible floor. Except as provided for in Sections 1110.2.2 through 1110.2.6, at least one of each type of fixture, element, control, or dispenser in each accessible toilet room and bathing room shall be accessible.
G. Add Section 1110.2.6 to the IBC to read:
1110.2.6 Multi-user gender-neutral toilet facility fixtures. Where multi-user facilities are provided to serve all genders, at least two of each fixture type, but only one urinal if more than one urinal is provided, shall comply with ICC A117.1. Water closet and urinal compartments shall comply with Section 1210.3.
H. Add Sections 1110.17 and 1110.17.1 to the IBC to read:
1110.17 Dwellings containing universal design features for accessibility. Group R-5 occupancies not subject to Section R320.1 of the IRC and Group R-3 occupancies not subject to Section 1108.6.3 may comply with this section and be approved by the local building department as dwellings containing universal design features for accessibility.
1110.17.1 Standards for dwellings containing universal design features for accessibility. When the following requirements are met, approval shall be issued by the local building department indicating that a dwelling has been constructed in accordance with these standards and is deemed to be a dwelling containing universal design features for accessibility.
1. The dwelling must comply with the requirements for Type C units under Section 1105 of ICC A117.1 with the following changes to those requirements:
1.1. That at least one bedroom be added to the interior spaces required by Section 1105.4 of ICC A117.1.
1.2. In the toilet room or bathroom required by Section 1105 of ICC A117.1, in addition to the lavatory and water closet, a shower or bathtub complying with Section 1104.11.3.2.3 of ICC A117.1 shall be provided and shall include reinforcement for future installation of grab bars in accordance with Section 1104.11.1 of ICC A117.1.
1.3. That the exception to Section 1105.4 of ICC A117.1 is not applicable.
1.4. That there be a food preparation area complying with Section 1105.7 of ICC A117.1 on the entrance level.
1.5. That any thermostat for heating or cooling on the entrance level comply with Section 1102.9 of ICC A117.1.
I. Delete the exception for Item 1 of Section 1112.1 of the IBC.

13 Va. Admin. Code § 5-63-250

Derived from Virginia Register Volume 22, Issue 3, eff. November 16, 2005; amended, Virginia Register Volume 24, Issue 14, eff. May 1, 2008; Volume 27, Issue 2, eff. March 1, 2011; Change in Effective Date, 27:5 VA.R. 534 November 8, 2010; Amended, Virginia Register Volume 30, Issue 16, eff. July 14, 2014; Amended, Virginia Register Volume 34, Issue 18, eff. 9/4/2018; Amended, Virginia Register Volume 37, Issue 14, eff. 7/1/2021; Amended, Virginia Register Volume 40, Issue 9, eff. 1/18/2024.

Statutory Authority: § 36-98 of the Code of Virginia.