12 Va. Admin. Code § 5-635-320
TABLE 5 Minimum operator visit frequency for rainwater harvesting systems | ||
End Use Tier | Initial Inspection | Regular Inspection Schedule |
1 | Prior to the system entering service | As needed |
2, 3 | Prior to the system entering service | Every 12 months while structure is occupied. If system only provides water for outdoor use, then as needed |
4 (single service connection) | Condition of issuance of operation permit | Every 180 calendar days while structure is occupied* |
4 (multiple service connections) | Condition of issuance of operation permit | Every 90 calendar days while any connection serves an occupied structure* |
*If a structure is vacant longer than the regular inspection cycle in Table 5, an operator shall inspect the rainwater harvesting system prior to the structure becoming reoccupied. |
12 Va. Admin. Code § 5-635-320
Statutory Authority: §§ 32.1-12 and 32.1-248.2 of the Code of Virginia.