Current through Register Vol. 41, No. 8, December 2, 2024
Section 12VAC5-630-430 - DisinfectionA. Private wells shall be disinfected before placing the well in service.B. Methodology. Disinfection shall be accomplished by one of the following methods: 1. Maintaining a 100 mg/l solution of chlorine in the well for 24 hours utilizing the dosage rates set forth in 12VAC5-630-470.2. Applying a quantity of water/chlorine solution to ensure a minimum of 100 mg/L of available chlorine throughout the well and immediate formation materials. Disinfection contact time shall be established on the basis of contact units, which are calculated as mg/L chlorine multiplied by hours of exposure. Contact time shall equate to a minimum of 1,000 contact units (50 mg/L chlorine x 20 hours = 1,000 contact units; 200 mg/L chlorine x 5 hours = 1,000 contact units; etc.).12 Va. Admin. Code § 5-630-430
Derived from VR355-34-100 §3.9, eff. April 1, 1992; Amended, Virginia Register Volume 41, Issue 04, eff. 11/6/2024.Statutory Authority: §§ 32.1-12 and 32.1-176 of the Code of Virginia.