Section 12VAC5-590-580 - General requirements for cross-connection control and backflow prevention
A. Every owner shall establish and enforce a cross-connection control program (CCCP) in accordance with 12VAC5-590-360. The goal of the CCCP is to prevent the intrusion of contamination into the distribution system via cross-connections and backflow. The owner shall document the CCCP activities in a cross-connection control plan and submit the written document to the department for review and approval.
B. No owner shall install, maintain, or allow a service connection to any premises where cross-connections to a waterworks or a consumer's water system exist, unless the owner and department ensure the cross-connections are adequately safeguarded.
C. No owner shall install, maintain, or allow any connection whereby water from an auxiliary water system may enter a waterworks or consumer's water system, unless the owner and department approve the auxiliary water system, the method of connection, and use of such system.
D. The owner, in accordance with 12VAC5-590-510 C, shall maintain acceptable working pressures in the distribution system to reduce the potential for backflow to occur.