(3) The residual disinfectant concentration in the distribution system, measured as total chlorine, free chlorine, combined chlorine, or chlorine dioxide, shall not be undetectable in more than 5% of the samples each month, for any two consecutive months that the waterworks serves water to the public. If the department determines that a waterworks is experiencing excessive coliform occurrences in its distribution system, then the department may require the owner to maintain minimum chlorine residual levels of 0.2 mg/L or monochloramine levels of 0.5 mg/L throughout the distribution system. Water in the distribution system with a heterotrophic bacteria concentration less than or equal to 500/mL, measured as HPC, is deemed to have a detectable residual disinfectant for the purposes of determining compliance with this requirement. Thus, the value "V," in percent, in the following formula shall not exceed 5% in one month, for any two consecutive months. V = [(c + d + e) / (a + b)] X 100
where
a = number of instances where the residual disinfectant concentration is measured;
b = number of instances where the residual disinfectant concentration is not measured but HPC is measured;
c = number of instances where the residual disinfectant concentration is measured but not detected and no HPC is measured;
d = number of instances where no residual disinfectant concentration is detected and where the HPC is greater than 500/mL; and
e = number of instances where the residual disinfectant concentration is not measured and HPC is greater than 500/mL.