12 Va. Admin. Code § 5-590-388

Current through Register Vol. 40, No. 22, June 17, 2024
Section 12VAC5-590-388 - Radiological compliance
A. MCLGs for radionuclides are listed in Table 546.1 of 12VAC5-590-546 B.
B. PMCLs for radionuclides are applicable to community waterworks only and are listed in Table 340.4. Compliance with PMCLs will be determined based on the analytical results obtained at each entry point. If the sample result at one entry point exceeds the PMCL, then the owner is in violation of the PMCL.
1. For the owner that is monitoring more than once per year, compliance with the PMCL is determined by an RAA of the analytical results at each entry point. If the average result at any entry point is greater than the PMCL, then the waterworks is out of compliance with the PMCL.
2. For the owner of a waterworks that monitors more than once per year, if any sample result will cause the RAA to exceed the PMCL at any entry point, then the waterworks is out of compliance with the PMCL immediately.
3. All samples collected and analyzed under the provisions 12VAC5-590-378 shall be included in determining compliance, even if that number is greater than the minimum required.
4. If the owner does not collect all required samples when compliance is based on an RAA result of quarterly samples, then compliance will be based on the RAA result of the samples collected.
5. If a sample result is less than the detection limit as specified in Table 378.1, then zero will be used to calculate the RAA unless a gross alpha particle activity result is being used instead of radium-226 or uranium. If the gross alpha particle activity result is less than the detection limit as specified in Table 378.1, then one half the detection limit will be used to calculate the RAA.
C. Radiological (gross alpha, combined radium-226 and radium-228, uranium, and man-made radioactivity).
1. Compliance with the radiological PMCLs shall be based on the RAA results. PMCLs are indicated in Table 340.4. Sampling for radiological analysis shall be in compliance with 12VAC5-590-378.
2. Compliance shall be determined by rounding off results to the same number of significant figures as the PMCL for the radionuclide in question.
D. If a PMCL for radioactivity listed in Table 340.4 is exceeded, then the owner shall give notice to the department pursuant to 12VAC5-590-530 and to the public as required by 12VAC5-590-540 A 2.

12 Va. Admin. Code § 5-590-388

Derived from Virginia Register Volume 37, Issue 20, eff. 6/23/2021.

Statutory Authority: §§ 32.1-12 and 32.1-170 of the Code of Virginia.