TABLE 374.1 Monitoring Frequency by Source Water Type for TTHM and HAA5 | |||
SOURCE WATER TYPE | POPULATION SIZE CATEGORY | MONITORING FREQUENCYa | DISTRIBUTION SYSTEM MONITORING LOCATION TOTAL PER MONITORING PERIODb |
Surface water or GUDI Source | Less than 500 | per year | 2 |
500 - 3,300 | per quarter | 2 | |
3,301 - 9,999 | per quarter | 2 | |
10,000 - 49,999 | per quarter | 4 | |
50,000 - 249,999 | per quarter | 8 | |
250,000 - 999,999 | per quarter | 12 | |
1,000,000 - 4,999,999 | per quarter | 16 | |
Equal to or greater than 5,000,000 | per quarter | 20 | |
Groundwater | Less than 500 | per year | 2 |
500 - 9,999 | per year | 2 | |
10,000 - 99,999 | per quarter | 4 | |
100,000 - 499,999 | per quarter | 6 | |
Equal to or greater than 500,000 | per quarter | 8 | |
aThe owner shall monitor during the month of highest DBP concentrations. bThe owner of a waterworks on quarterly monitoring (except those using a surface water source, a GUDI source, or both and serving 500 to 3,300 people) shall collect dual sample sets every 90 days at each monitoring location. A groundwater system serving 500 to 9,999 people shall collect dual sample sets annually at each monitoring location. A waterworks serving fewer than 500 people and a waterworks using a surface water source, a GUDI source, or both and serving 500 to 3,300 people shall collect individual TTHM and HAA5 samples (instead of a dual sample set) at the locations with the highest TTHM and HAA5 concentrations, respectively. A waterworks serving fewer than 500 people shall sample annually, and a waterworks using a surface water source, a GUDI source, or both and serving 500 to 3,300 people shall sample every 90 days. For a waterworks serving fewer than 500 people, only one location with a dual sample set per monitoring period is needed if the highest TTHM and HAA5 concentrations occur at the same location (and month, if monitoring annually). |
TABLE 374.2 Reduced Monitoring for TTHM and HAA5 | |||
SOURCE WATER TYPE | POPULATION SIZE CATEGORY | MONITORING FREQUENCYa | DISTRIBUTION SYSTEM MONITORING LOCATION PER MONITORING PERIOD |
Surface water or GUDI Source | Less than 500 | Monitoring may not be reduced. | |
500 - 3,300 | per year | One TTHM and one HAA5 sample: one at the location and during the quarter with the highest TTHM single measurement, one at the location and during the quarter with the highest HAA5 single measurement; one dual sample set per year if the highest TTHM and HAA5 measurements occurred at the same location and quarter. | |
3,301 - 9,999 | per year | Two dual sample sets: one at the location and during the quarter with the highest TTHM single measurement, one at the location and during the quarter with the highest HAA5 single measurement. | |
10,000 - 49,999 | per quarter | Two dual sample sets: at the locations with the highest TTHM and highest HAA5 LRAAs. | |
50,000 - 249,999 | per quarter | Four dual sample sets: at the locations with the two highest TTHM and two highest HAA5 LRAAs. | |
250,000 - 999,999 | per quarter | Six dual sample sets: at the locations with the three highest TTHM and three highest HAA5 LRAAs. | |
1,000,000 - 4,999,999 | per quarter | Eight dual sample sets: at the locations with the four highest TTHM and four highest HAA5 LRAAs. | |
Equal to or greater than 5,000,000 | per quarter | Ten dual sample sets: at the locations with the five highest TTHM and five highest HAA5 LRAAs. | |
Groundwater | Less than 500 | every third year | One TTHM and one HAA5 sample: one at the location and during the quarter with the highest TTHM single measurement, one at the location and during the quarter with the highest HAA5 single measurement; one dual sample set per year if the highest TTHM and HAA5 measurements occurred at the same location and quarter. |
500 - 9,999 | per year | One TTHM and one HAA5 sample: one at the location and during the quarter with the highest TTHM single measurement, one at the location and during the quarter with the highest HAA5 single measurement; one dual sample set per year if the highest TTHM and HAA5 measurements occurred at the same location and quarter. | |
10,000 - 99,999 | per year | Two dual sample sets: one at the location and during the quarter with the highest TTHM single measurement, one at the location and during the quarter with the highest HAA5 single measurement. | |
100,000 - 499,999 | per quarter | Two dual sample sets: at the locations with the highest TTHM and highest HAA5 LRAAs. | |
Equal to or greater than 500,000 | per quarter | Four dual sample sets: at the locations with the two highest TTHM and two highest HAA5 LRAAs. | |
aThe owner of a waterworks on quarterly monitoring shall collect dual sample sets every 90 days. |
12 Va. Admin. Code § 5-590-374
Statutory Authority: §§ 32.1-12 and 32.1-170 of the Code of Virginia.