Section 12VAC5-590-1020 - LocationA. The pumping station shall be located to meet the hydraulic needs of the distribution system, preserve the quality of the water pumped, and shall consider the availability of a power or a fuel supply.B. The station shall be: 1. Elevated to a minimum of one foot above the 100-year flood elevation or protected to that elevation;2. Accessible at all times unless allowed to be out of service by the department;3. Graded around the station so as to lead surface drainage away from the station; and4. Protected to prevent vandalism and entrance by animals or unauthorized persons.12 Va. Admin. Code § 5-590-1020
Derived from VR355-18-010.02 § 3.39, eff. August 1, 1991; Amended, Virginia Register Volume 37, Issue 20, eff. 6/23/2021.Statutory Authority: §§ 32.1-12 and 32.1-170 of the Code of Virginia.