Section 3 New Construction Rules Commencing with transactions financed by proceeds of the Agency's Single Family Mortgage Purchase Bonds, 1980 Series A, and in addition to all other Agency requirements, New Construction securing mortgage loans purchased by the Agency shall be designed to meet, and shall meet, all of the energy conservation standards set forth below:
(i) Attic or ceiling insulation shall be R-38 (i.e. 12" of fiberglass or equivalent).(ii) Outside walls shall be insulated to R-19 (i.e. 6" of fiberglass or equivalent).(iii) Floors of heated space over unheated crawl spaces, unheated basements and/or unheated garage areas (those not containing a primary heating plant) shall be insulated to R-19. All floor joists headers/rim joists shall be insulated to R-11.(iv) Vapor barriers must be properly installed to prevent moisture damage.(v) Continuous soffit and ridge venting is the recommended method for ventilating attic areas. Properly sized gable end vents may be substituted for continuous ridge vents.(vi) Windows shall be double or triple glazed. Metal windows shall have a thermal break. Single glazed windows are acceptable with the installation of a storm window. All windows must be weather stripped.(vii) All exterior doors shall be insulated and weather stripped. A storm door is required when the primary door is a hollow core door or is over 25% glass.(viii) All exterior joints and openings shall receive proper caulking or sealant to prevent air infiltration.(ix) Maximum practical solar orientation shall be employed which includes minimum window area to the north and maximum window area to the south.