Section R710-11-7 - Amendments and Additions(1) At the time of service, all servicing shall be done in accordance with the adopted NFPA standard, adopted statutes, and these rules.(2) Fire alarm systems shall be inspected annually by a person holding the appropriate certificate of registration as required in Section R710-11-4(1).(3) Newly installed fire alarm systems are exempt from the annual testing requirement required in Section R710-11-7(2), for one year from the approval date of the initial installation acceptance testing.Utah Admin. Code R710-11-7
Amended by Utah State Bulletin Number 2016-18, effective 8/23/2016