Utah Admin. Code 614-4-6

Current through Bulletin 2024-12, June 15, 2024
Section R614-4-6 - Electrical
A. All electrical switches, controls, motors, wiring and equipment located in explosive material plants shall conform to the requirements of 29 CFR 1910 Chapter S (Electrical).
B. In any operations where a continuous supply of power is required, the lack of which may cause a hazard to employees an alternate source of power shall be provided.
C. The primary electrical supply to an explosives area shall be so arranged that it can be cut off by switches located at one or more central points away from the area.
D. When static electricity is a hazard nonsparking conductive floors and work surfaces or other approved methods to control and disperse static electricity is required, continuity of grounding on all mechanical devices shall be assured.
E. Only artificial lighting devices approved for the location shall be permitted in explosive areas.

Utah Admin. Code R614-4-6