TABLE 1 CONSTRUCTION REQUIREMENTS SUMMARY | ||||
LEVEL I | LEVEL II | LEVEL III | LEVEL IV | |
Number of. residents | 1 -16 | 4 -16 | 4 -16 | 4-16 |
Are residents Capable of Unassisted Self Preservation? | No, they are non ambulatory non-mobile | No, they are non ambulatory non-mobile | Yes, they are ambulatory mobile | Yes, they are ambulatory mobile |
What are resident's exit ability in an emergency | Restricted, physical or mental disability and medical condition | Restricted, physical or mental disability | Restricted, chemical or physical restraints | Not restricted |
Percentage of accessible rooms required | 100% | 10% or 100% if Physical Rehab. | 10% | 10% |
Construction Requirements code or regulation | NFPA 101 | NFPA 101 | NFPA 101 | Utah Fire Prevention Board Rule R710-3; IBC R-4 occupancy |
Fire rating of construction | 1 hour | 1 hour | 1 hour | No requirement |
Sprinkler required? | Yes | Yes | Yes | Only if bldg.. larger than 4,500 SF |
Smoke detector required? | Yes | Yes | Yes | Yes |
Manual fire alarm required? | Yes | Yes | Yes | Yes |
Above 3 systems required to be interconnected | Yes | Yes | Yes | No |
Corridor width required | 8 feet | 6 feet` | 5 feet | As required by IBC |
Resident room door width required | 44 inch | 44 inch | 36 inch | 36 inch |
Nurse call system required? | Yes | Yes | Optional | yes |
Utah Admin. Code R432-12-5