Section R315-103-3 - Commercial Hazardous Waste Facility Siting Criteria - Land Use Compatibility and Location
(a) Siting of commercial hazardous waste treatment, storage, and disposal facilities, including commercial hazardous waste incinerators, is prohibited within:
(1) national, state, and county parks, monuments, and recreation areas; designated wilderness and wilderness study areas; wild and scenic river areas;
(2) ecologically and scientifically significant natural areas, including but not limited to, wildlife management areas and habitat for listed or proposed endangered species as designated pursuant to the Endangered Species Act of 1982;
(3) 100 year floodplains, unless, for non-land based facilities only, the conditions found in subsection R315-264-18 are met to the satisfaction of the Director;
(4) 200 ft. of Holocene faults;
(5) underground mines, salt domes and salt beds;
(6) dam failure flood areas;
(7) areas likely to be impacted by landslide, mudflow, or other earth movement;
(8) farmlands classified or evaluated as "prime," "unique," or of "statewide importance" by the U.S. Department of Agriculture Soil Conservation Service under the Prime Farmland Protection Act;
(9) areas above aquifers containing ground water which has a total dissolved solids (TDS) content of less than 500 mg/l and which does not exceed applicable ground water quality standards for any contaminant. Land disposal facilities are also prohibited above aquifers containing ground water which has a TDS content of less than 3000 mg/l and which does not exceed applicable ground water quality standards for any contaminant. Non-land-based facilities above aquifers containing ground water which has a TDS content of 500 to 3000 mg/l and all facilities above aquifers containing ground water which has a TDS content between 3000 and 10,000 mg/l are permitted only where the depth to ground water is greater than 100 ft. The applicant for the proposed facility shall make the demonstration of ground water quality necessary to determine the appropriate aquifer classification;
(10) recharge zones of aquifers containing ground water which has a TDS content of less than 3000 mg/l. Land disposal facilities are also prohibited in recharge zones of aquifers containing ground water which has a TDS content of less than 10,000 mg/l;
(11) designated drinking water source protection areas or, if no source protection area is designated, a distance to existing drinking water wells and watersheds for public water supplies of one year ground water travel time plus 1000 feet for non-land-based facilities and five years ground water travel time plus 1000 feet for land disposal facilities. This requirement does not include on-site facility operation wells. The applicant for the proposed facility shall make the demonstration, acceptable to the Director, of hydraulic conductivity and other information necessary to determine the one or five year ground water travel distance as applicable. The facility operator may be required to conduct vadose zone or other near surface monitoring if determined to be necessary and appropriate by the Director;
(12) five miles of existing permanent dwellings, residential areas, and other incompatible structures including, but not limited to, schools, churches, and historic structures;
(13) five miles of surface waters including intermittent streams, perennial streams, rivers, lakes, reservoirs, estuaries, and wetlands; and
(14) 1000 ft. of archeological sites to which adverse impacts cannot reasonably be mitigated.

Utah Admin. Code R315-103-3