Utah Admin. Code 313-30-4

Current through Bulletin 2024-08, April 15, 2024
Section R313-30-4 - General Technical Requirements for Facilities Using Therapeutic Radiation Machines
(1) Protection Surveys.
(a) The registrant shall ensure that radiation protection surveys of new facilities, and existing facilities not previously surveyed are performed with an operable radiation measurement survey instrument calibrated in accordance with R313-30-8. The radiation protection survey shall be performed by, or under the direction of, a Radiation Therapy Physicist or a Certified Health Physicist and shall verify that, with the therapeutic radiation machine in a "BEAM- ON" condition, with the largest clinically available treatment field and with a scattering phantom in the useful beam of radiation:
(i) Radiation levels in restricted areas are not likely to cause personnel exposures in excess of the limits specified in R313-15-201(1); and
(ii) Radiation levels in unrestricted areas do not exceed the limits specified in R313-15-301(1).
(b) In addition to the requirements of R313-30-4(1)(a), a radiation protection survey shall also be performed prior to subsequent medical use and:
(i) After making changes in the treatment room shielding;
(ii) After making changes in the location of the therapeutic radiation machine within the treatment room;
(iii) After relocation of, or modification of, the therapeutic radiation machine; or
(iv) Before using the therapeutic radiation machine in a manner that could result in increased radiation levels in areas outside the external beam radiation therapy treatment room.
(c) The survey record shall indicate instances where the facility, in the opinion of the Radiation Therapy Physicist or a Certified Health Physicist, is in violation of applicable radiation protection rules. The survey record shall also include the date of the measurements, the reason the survey is required, the manufacturer's name, model number and serial number of the therapeutic radiation machine, the instruments used to measure radiation levels, a plan of the areas surrounding the treatment room that were surveyed, the measured dose rate at several points in areas expressed in microsieverts, millirems, per hour, the calculated maximum level of radiation over a period of one week for restricted and unrestricted areas, and the signature of the individual responsible for conducting the survey;
(d) If the results of the surveys required by R313-30-4(1)(a) or R313-30-4(1)(b) indicate radiation levels in excess of the respective limit specified in R313-30-4(1)(a), the registrant shall lock the control in the "OFF" position and not use the unit:
(i) Except as may be necessary to repair, replace, or test the therapeutic radiation machine, the therapeutic radiation machine shielding, or the treatment room shielding; or
(ii) Until the registrant has received a written approval from the Director.
(2) Modification of Radiation Therapy Unit or Room Before Beginning a Treatment Program. If the survey required by R313-30-4(1) indicates that an individual in an unrestricted area may be exposed to levels of radiation greater than those permitted by R313-15-301(1) of these rules, before beginning the treatment program the registrant shall:
(a) Either equip the unit with beam direction interlocks or add additional radiation shielding to ensure compliance with R313-15-301(1) of these rules;
(b) Perform the survey required by R313-30-4(1) again; and
(c) Include in the report required by R313-30-4(4) the results of the initial survey, a description of the modification made to comply with R313-30-4(2)(a), and the results of the second survey; or
(d) Request and receive a registration amendment under R313-15-301(3) of these rules that authorizes radiation levels in unrestricted areas greater than those permitted by R313-15-301(1) of these rules.
(3) Possession of Survey Instruments. Facility locations authorized to use a therapeutic radiation machine in accordance with R313-30-6 and R313-30-7 shall possess appropriately calibrated portable monitoring equipment. As a minimum, the equipment shall include a portable radiation measurement survey instrument capable of measuring dose rates over the range 10 uSv (1 mrem) per hour to 10 mSv (1000 mrem) per hour. The survey instruments shall be operable and calibrated in accordance with R313-30-8.
(4) Reports of External Beam Radiation Therapy Surveys and Measurements. The registrant for a therapeutic radiation machine subject to R313-30-6 or R313-30-7 shall furnish a copy of the records required in R313-30-4(1) and R313-30-4(2) to the Director within 30 days following completion of the action that initiated the record requirement.

Utah Admin. Code R313-30-4