Utah Admin. Code 309-525-7

Current through Bulletin 2024-12, June 15, 2024
Section R309-525-7 - Plant Reliability

Plants designed for processing surface water or ground water under direct influence of surface water shall be designed to meet present and future water demands and assure reliable operation at all times. To help assure proper, uninterrupted operation:

(1) A manual override shall be provided for any automatic controls. Highly sophisticated automation may put proper maintenance beyond the capability of the plant operator, leading to equipment breakdowns or expensive servicing. Adequate funding must be assured for maintenance of automatic equipment.
(2) Main switch electrical controls shall be located above grade, in areas not subject to flooding.
(3) Plants shall be operated by qualified personnel approved by the Director. As a minimum, the treatment plant manager is required to be certified in accordance with R309-300 at the grade of the waterworks system with an appropriate unrestricted Utah Operator's Certificate.
(4) The plant shall be constructed to permit units to be taken out of service without disrupting operation, and with drains or pumps sized to allow dewatering in a reasonable period of time.
(5) The plant shall have standby power available to permit operation of essential functions during power outages,
(6) The plant shall be provided with backup equipment or necessary spare parts for all critical items.
(7) Individual components critical to the operation of a treatment plant shall be provided with anchorage to secure the components from loss due to an earthquake event.

Utah Admin. Code R309-525-7