Utah Admin. Code 309-230-6

Current through Bulletin 2024-12, June 15, 2024
Section R309-230-6 - Immediate Response

If a sample equals or exceeds a lead concentration of five parts per billion:

(1) A school or child care center shall prevent use of the consumable tap that equals or exceeds a lead concentration of fifteen parts per billion within 24 hours after receiving the sample test result;
(2) A school or child care center may develop and implement a flushing plan for a consumable tap with a lead concentration equal to or greater than five and less than fifteen parts per billion until remediation and retesting is completed in accordance with Section R309-230-7; and
(3) A school or child care center may apply for reimbursement for costs associated with the purchase of bottled water with the Division of Drinking Water until a permanent control measure is implemented.

Utah Admin. Code R309-230-6

Adopted by Utah State Bulletin Number 2022-22, effective 11/1/2022