Utah Admin. Code 307-327-4

Current through Bulletin 2024-23, December 1, 2024
Section R307-327-4 - General Requirements
(1) Any existing stationary storage tank, reservoir or other container with a capacity greater than 40,000 gallons (150,000 liters) that is used to store volatile petroleum liquids with a true vapor pressure greater than 10.5 kilo pascals (kPa) (1.52 psia) at storage temperature shall be fitted with control equipment that will minimize vapor loss to the atmosphere. Storage tanks, except those erected before January 1, 1979, which are equipped with external floating roofs, shall be fitted with an internal floating roof that shall rest on the surface of the liquid contents and shall be equipped with a closure seal or seals to close the space between the roof edge and the tank wall, or alternative equivalent controls, provided the design and effectiveness of such equipment is documented and submitted to and approved by the director. The owner or operator shall maintain a record of the type and maximum true vapor pressure of stored liquid.
(2) The owner or operator of a petroleum liquid storage tank not subject to (1) above, but containing a petroleum liquid with a true vapor pressure greater than 7.0 kPa (1.0 psia), shall maintain records of the average monthly storage temperature, the type of liquid, throughput quantities, and the maximum true vapor pressure.

Utah Admin. Code R307-327-4