30 Tex. Admin. Code § 217.300

Current through Reg. 49, No. 25; June 21, 2024
Section 217.300 - Post-Disinfection Requirements
(a) Sample points. Sampling points must be identified in the engineering report. A design must include a sufficient number of sampling points to:
(1) allow an operator to monitor the disinfection system for process control; and
(2) allow monitoring of permitted effluent limits.
(b) Dissolved Oxygen Requirements. A wastewater treatment facility must be designed with the ability to add post-aeration if needed to meet effluent limits for dissolved oxygen in the wastewater permit. If the wastewater permit requires a minimum dissolved oxygen of 5.0 milligrams per liter or greater, the engineering report must include calculations that demonstrate how the post-aeration system will maintain the minimum dissolved oxygen level.

30 Tex. Admin. Code § 217.300

The provisions of this §217.300 adopted to be effective August 28, 2008, 33 TexReg 6843; Amended by Texas Register, Volume 40, Number 47, November 20, 2015, TexReg 8340, eff. 12/4/2015