30 Tex. Admin. Code § 217.277

Current through Reg. 49, No. 25; June 21, 2024
Section 217.277 - Requirements for One-Ton and Larger Cylinders used in Liquid-Withdrawal Chlorine Disinfection and Sulfur Dioxide Dechlorination Systems
(a) Heated Rooms. The chlorinators and sulfonators must be located indoors at a minimum room temperature of 65 degrees Fahrenheit.
(b) Outdoor Storage. The chlorine and sulfur dioxide cylinders for systems using liquid withdrawal may be stored outdoors without reducing the withdrawal rates calculated from § 217.273(a)(2) of this title (relating to Cylinder Requirements for Gaseous Chlorine Disinfection and Sulfur Dioxide Dechlorination Systems).
(c) Separation. The separation requirements for a one-ton cylinder liquid-withdrawal systems are the same as those for a one-ton cylinder gas-withdrawal system under § 217.278(e) of this title (relating to Safety Requirements for Gaseous Chlorine Disinfection and Sulfur Dioxide Dechlorination Systems).

30 Tex. Admin. Code § 217.277

The provisions of this §217.277 adopted to be effective August 28, 2008, 33 TexReg 6843; Amended by Texas Register, Volume 40, Number 47, November 20, 2015, TexReg 8339, eff. 12/4/2015