30 Tex. Admin. Code § 217.122

Current through Reg. 49, No. 25; June 21, 2024
Section 217.122 - Fine Screens
(a) A fine screen may be used in lieu of a coarse screen.
(b) The clear openings in a fine screen must be less than 0.25 inch.
(c) Any five-day biochemical oxygen demand (BOD5) reduction percentage claimed for a fine screen must be developed through a study conducted on actual full-scale operation of the proposed fine screen. The BOD5 reduction percentage claimed must not exceed 35%.
(d) The engineering report must justify any reduction in the size of a treatment unit that is based on removal of BOD5 by a fine screen.
(e) An owner who claims a BOD5 reduction credit must include a sufficient number of fine screen units so that any BOD5 reduction claimed will be met with the largest fine screen unit out of service.
(f) A design may include a single fine screen unit only if the design includes an emergency overflow channel with a coarse screen to accept flow when the fine screen is out of service. No BOD5 removal credit is allowed with a single fine screen design.
(g) A coarse screen must be provided ahead of a fine screen when the manufacturer of a fine screen recommends prescreening before the fine screen.
(h) A moving or rotating fine screen must use a continuous cleaning device, such as water jets or wiper blades.
(i) A fine screen unit must automatically convey the screenings to a storage area or processing unit that complies with § 217.123 of this title (relating to Screenings and Debris Handling).
(j) A fine screen must meet the manufacturer's recommendations with respect to velocity and head loss through the fine screen.
(k) A fine screen must use either a bar rack or a perforated plate.

30 Tex. Admin. Code § 217.122

The provisions of this §217.122 adopted to be effective August 28, 2008, 33 TexReg 6843; Amended by Texas Register, Volume 40, Number 47, November 20, 2015, TexReg 8315, eff. 12/4/2015