30 Tex. Admin. Code § 116.620

Current through Reg. 49, No. 43; October 25, 2024
Section 116.620 - Installation and/or Modification of Oil and Gas Facilities
(a) Emission specifications.
(1) Venting or flaring more than 0.3 long tons per day of total sulfur shall not be allowed.
(2) No facility shall be allowed to emit total uncontrolled emissions of sulfur compounds, except sulfur dioxide (SO 2), from all vents (excluding process fugitives emissions) equal to or greater than four pounds per hour unless the vapors are collected and routed to a flare.
(3) Any vent, excluding any safety relief valves that discharge to the atmosphere only as a result of fire or failure of utilities, emitting sulfur compounds other than SO2 shall be at least 20 feet above ground level.
(4) New or modified internal combustion reciprocating engines or gas turbines permitted under this standard permit shall satisfy all of the requirements of § 106.512 of this title (relating to Stationary Engines and Turbines), except that registration using the Form PI-7 or PI-8 shall not be required. Emissions from engines or turbines shall be limited to the amounts found in § 106.4(a)(1) of this title (relating to Requirements for Permitting by Rule).
(5) Total Volatile Organic Compound (VOC) emissions from a natural gas glycol dehydration unit shall not exceed ten tons per year (tpy) unless the vapors are collected and controlled in accordance with subsection (b)(2) of this section.
(6) Any combustion unit (excluding flares, internal combustion engines, or natural gas turbines), with a design maximum heat input greater than 40 million British thermal units (Btu) per hour (using lower heating values) shall not emit more than 0.06 pounds of nitrogen oxides per million Btu.
(7) No facility which is less than 500 feet from the nearest off-plant receptor shall be allowed to emit uncontrolled VOC process fugitive emissions equal to or greater than ten tpy, but less than 25 tpy, unless the equipment is inspected and repaired according to subsection (c)(1) of this section.
(8) No facility which is 500 feet or more from the nearest off-plant receptor shall be allowed to emit uncontrolled VOC process fugitive emissions equal to or greater than 25 tpy unless the equipment is inspected and repaired according to subsection (c)(1) of this section.
(9) No facility which is less than 500 feet from the nearest off-plant receptor shall be allowed to emit uncontrolled VOC process fugitive emissions equal to or greater than 25 tpy unless the equipment is inspected and repaired according to subsection (c)(2) of this section.
(10) No facility shall be allowed to emit uncontrolled VOC process fugitive emissions equal to or greater than 40 tpy unless the equipment is inspected and repaired according to subsection (c)(2) of this section.
(11) No facility which is located less than 1/4 mile from the nearest off-plant receptor shall be allowed to emit hydrogen sulfide H2 S or SO2 process fugitive emissions unless the equipment is inspected and repaired according to subsection (c)(3) of this section. No facility which is located at least 1/4 mile from the nearest off-plant receptor shall be allowed to emit H 2 S or SO2 process fugitive emissions unless the equipment is inspected and repaired according to subsection (c)(3) of this section or unless the H2 S or SO 2 emissions are monitored with ambient property line monitors according to subsection (e)(1) of this section. Components in sweet crude oil or gas service as defined by Chapter 101 of this title (relating to General Air Quality Rules) are exempt from these limitations.
(12) Flares shall be designed and operated in accordance with 40 Code of Federal Regulations (CFR), Part 60.18 or equivalent standard approved by the commission, including specifications of minimum heating values of waste gas, maximum tip velocity, and pilot flame monitoring. If necessary to ensure adequate combustion, sufficient gas shall be added to make the gases combustible. An infrared monitor is considered equivalent to a thermocouple for flame monitoring purposes. An automatic ignition system may be used in lieu of a continuous pilot.
(13) Appropriate documentation shall be submitted to demonstrate that compliance with the Prevention of Significant Deterioration (PSD) and nonattainment new source review provisions of the FCAA, Parts C and D, and regulations promulgated thereunder, and with Subchapter C of this chapter (relating to Hazardous Air Pollutants: Regulations Governing Constructed or Reconstructed Major Sources (FCAA, §112(g), 40 CFR Part 63)) are being met. The oil and gas facility shall be required to meet the requirements of Subchapter B of this chapter (relating to New Source Review Permits) instead of this subchapter if a PSD or nonattainment permit or a review under Subchapter C of this chapter is required.
(14) Documentation shall be submitted to demonstrate compliance with applicable New Source Performance Standards (NSPS, 40 CFR Part 60).
(15) Documentation shall be submitted to demonstrate compliance with applicable National Emission Standards for Hazardous Air Pollution (NESHAP, 40 CFR Part 61).
(16) Documentation shall be submitted to demonstrate compliance with applicable maximum achievable control technology standards as listed under 40 CFR Part 63, promulgated by the EPA under FCAA, §112 or as listed in Chapter 113, Subchapter C of this title (relating to National Emissions Standards for Hazardous Air Pollutants for Source Categories (FCAA §112, 40 CFR Part 63)).
(17) New and increased emissions shall not cause or contribute to a violation of any National Ambient Air Quality Standard or regulation property line standards as specified in Chapters 111, 112, and 113 of this title (relating to Control of Air Pollution from Visible Emissions and Particulate Matter; Control of Air Pollution from Sulfur Compounds; and Control of Air Pollution from Toxic Materials). Engineering judgment and/or computerized air dispersion modeling may be used in this demonstration. To show compliance with § 116.610(a)(1) of this title (relating to Applicability) for H2 S emissions from process vents, ten milligrams per cubic meter shall be used as the "L" value instead of the value represented by § 116.610(a)(1) of this title.
(18) Fuel for all combustion units and flare pilots shall be sweet natural gas or liquid petroleum gas, fuel gas containing no more than ten grains of total sulfur per 100 dry standard cubic feet (dscf), or field gas. If field gas contains more than 1.5 grains of H 2 S or 30 grains total sulfur compounds per 100 dscf, the operator shall maintain records, including at least quarterly measurements of fuel H2 S and total sulfur content, which demonstrate that the annual SO2 emissions from the facility do not exceed the limitations listed in the standard permit registration. If a flare is the only combustion unit on a property, the operator shall not be required to maintain such records on flare pilot gas.
(b) Control requirements.
(1) Floating roofs or equivalent controls shall be required on all new or modified storage tanks, other than pressurized tanks which meet § 106.476 of this title (relating to Pressurized Tanks or Tanks Vented to Control), unless the tank is less than 25,000 gallons in nominal size or the vapor pressure of the compound to be stored in the tank is less than 0.5 pounds per square inch absolute (psia) at maximum short-term storage temperature.
(A) For internal floating roofs, mechanical shoe primary seal or liquid-mounted primary seal or a vapor-mounted primary with rim-mounted secondary seal shall be used.
(B) Mechanical shoe or liquid-mounted primary seals shall include a rim-mounted secondary seal on all external floating roofs tanks. Vapor-mounted primary seals will not be accepted.
(C) All floating roof tanks shall comply with the requirements under §115.112(a)(2)(A) - (F) of this title (relating to Control Requirements).
(D) In lieu of a floating roof, tank emissions may be routed to:
(i) a destruction device such that a minimum VOC destruction efficiency of 98% is achieved; or
(ii) a vapor recovery system such that a minimum VOC recovery efficiency of 95% is achieved.
(E) Independent of the permits by rule listed in this paragraph, if the emissions from any fixed roof tank exceed ten tpy of VOC or ten tpy of sulfur compounds, the tank emissions shall be routed to a destruction device, vapor recovery unit, or equivalent method of control that meets the requirements listed in subparagraph (D) of this paragraph.
(2) The VOC emissions from a natural gas glycol dehydration unit shall be controlled as follows.
(A) If total uncontrolled VOC emissions are equal to or greater than ten tpy, but less than 50 tpy, a minimum of 80% by weight minimum control efficiency shall be achieved by either operating a condenser and a separator (or flash tank), vapor recovery unit, destruction device, or equivalent control device.
(B) If total uncontrolled VOC emissions are equal to or greater than 50 tpy, a minimum of:
(i) 98% by weight minimum destruction efficiency shall be achieved by a destruction device or equivalent; or
(ii) 95% by weight minimum control efficiency shall be achieved by a vapor recovery system or equivalent.
(c) Inspection requirements.
(1) Owners or operators who are subject to subsection (a)(7) or (8) of this section shall comply with the following requirements.
(A) No component shall be allowed to have a VOC leak for more than 15 days after the leak is detected to exceed a VOC concentration greater than 10,000 parts per million by volume (ppmv) above background as methane, propane, or hexane, or the dripping or exuding of process fluid based on sight, smell, or sound for all components. The VOC fugitive emission components which contact process fluids where the VOCs have an aggregate partial pressure or vapor pressure of less than 0.5 psia at 100 degrees Fahrenheit are exempt from this requirement. If VOC fugitive emission components are in service where the operating pressure is at least 0.725 pounds per square inch (psi) (five kilopascals (Kpa)) below ambient pressure, then these components are also exempt from this requirement as long as the equipment is identified in a list that is made available upon request by the agency representatives, the EPA, or any other air pollution agency having jurisdiction. All piping and valves two inches nominal size and smaller, unless subject to federal NSPS requiring a fugitive VOC emissions leak detection and repair program or Chapter 115 of this title (relating to Control of Air Pollution from Volatile Organic Compounds), are also exempt from this requirement.
(B) All technically feasible repairs shall be made to repair a VOC leaking process fugitive component within 15 days after the leak is detected. If the repair of a component would require a unit shutdown, the repair may be delayed until the next scheduled shutdown. All leaking components which cannot be repaired until a scheduled shutdown shall be identified for such repair by tagging. The executive director, at his discretion, may require early unit shutdown or other appropriate action based on the number and severity of tagged leaks awaiting shutdown.
(C) New and reworked underground process pipelines containing VOCs shall contain no buried valves such that process fugitive emission inspection and repair is rendered impractical.
(D) To the extent that good engineering practice will permit, new and reworked valves and piping connections in VOC service shall be so located to be reasonably accessible for leak-checking during plant operation. Valves elevated more than two meters above a support surface will be considered non- accessible and shall be identified in a list to be made available upon request.
(E) New and reworked piping connections in VOC service shall be welded or flanged. Screwed connections are permissible only on piping smaller than two-inch diameter. No later than the next scheduled quarterly monitoring after initial installation or replacement, all new or reworked connections shall be gas-tested or hydraulically-tested at no less than normal operating pressure and adjustments made as necessary to obtain leak-free performance. Flanges in VOC service shall be inspected by visual, audible, and/or olfactory means at least weekly by operating personnel walk- through.
(F) Each open-ended valve or line in VOC service, other than a valve or line used for safety relief, shall be equipped with a cap, blind flange, plug, or a second valve. Except during sampling, the second valve shall be closed.
(G) Accessible valves in VOC service shall be monitored by leak-checking for fugitive emissions at least quarterly using an approved gas analyzer. For valves equipped with rupture discs, a pressure gauge shall be installed between the relief valve and rupture disc to monitor disc integrity. All leaking discs shall be replaced at the earliest opportunity, but no later than the next process shutdown. Sealless/leakless valves (including, but not limited to, welded bonnet bellows and diaphragm valves) and relief valves equipped with a rupture disc or venting to a control device are exempt from monitoring.
(H) Dual pump seals with barrier fluid at higher pressure than process pressure, seals degassing to vent control systems kept in good working order, or seals equipped with an automatic seal failure detection and alarm system, submerged pumps, or sealless pumps (including, but not limited to, diaphragm, canned, or magnetic driven pumps) are exempt from monitoring.
(I) All other pump and compressor seals emitting VOC shall be monitored with an approved gas analyzer at least quarterly.
(J) After completion of the required quarterly inspections for a period of at least two years, the operator of the oil and gas facility may request in writing to the Office of Permitting, Remediation, and Registration that the monitoring schedule be revised based on the percent of valves leaking. The percent of valves leaking shall be determined by dividing the sum of valves leaking during current monitoring and valves for which repair has been delayed by the total number of valves subject to the requirements. This request shall include all data that has been developed to justify the following modifications in the monitoring schedule.
(i) After two consecutive quarterly leak detection periods with the percent of valves leaking equal to or less than 2.0%, an owner or operator may begin to skip one of the quarterly leak detection periods for the valves in gas/vapor and light liquid service.
(ii) After five consecutive quarterly leak detection periods with the percent of valves leaking equal to or less than 2.0%, an owner or operator may begin to skip three of the quarterly leak detection periods for the valves in gas/vapor and light liquid service.
(2) Owners or operators who are subject to subsection (a)(9) or (10) of this section shall comply with the following requirements.
(A) No component shall be allowed to have a VOC leak for more than 15 days after the leak is found which exceeds a VOC concentration greater than 500 ppmv for all components except pumps and compressors and greater than 2,000 ppmv for pumps and compressors above background as methane, propane, or hexane, or the dripping or exuding of process fluid based on sight, smell, or sound. The VOC fugitive emission components which contact process fluids where the VOCs have an aggregate partial pressure or vapor pressure of less than 0.044 psia at 100 degrees Fahrenheit are exempt from this requirement. If VOC fugitive emission components are in service where the operating pressure is at least 0.725 psi (five Kpa) below ambient pressure, these components are also exempt from this requirement as long as the equipment is identified in a list that is made available upon request by agency representatives, the EPA, or any air pollution control agency having jurisdiction. All piping and valves two inches nominal size and smaller are also exempt from this requirement.
(B) All technically feasible repairs shall be made to repair a VOC leaking process fugitive component within 15 days after the leak is detected. If the repair of a component would require a unit shutdown, the repair may be delayed until the next scheduled shutdown. All leaking components which cannot be repaired until a scheduled shutdown shall be identified for such repair by tagging. The executive director, at his or her discretion, may require early unit shutdown or other appropriate action based on the number and severity of tagged leaks awaiting shutdown.
(C) New and reworked underground process pipelines containing VOCs shall contain no buried valves such that process fugitive emission inspection and repair is rendered impractical.
(D) To the extent that good engineering practice will permit, new and reworked valves and piping connections in VOC service shall be so located to be reasonably accessible for leak-checking during plant operation. Valves elevated more than two meters above a support surface will be considered non- accessible and shall be identified in a list to be made available upon request.
(E) New and reworked piping connections in VOC service shall be welded or flanged. Screwed connections are permissible only on piping smaller than two-inch diameter. No later than the next scheduled quarterly monitoring after initial installation or replacement, all new or reworked connections shall be gas-tested or hydraulically-tested at no less than normal operating pressure and adjustments made as necessary to obtain leak-free performance. Flanges in VOC service shall be inspected by visual, audible, and/or olfactory means at least weekly by operating personnel walk- through.
(F) Each open-ended valve or line in VOC service, other than a valve or line used for safety relief, shall be equipped with a cap, blind flange, plug, or a second valve. Except during sampling, the second valve shall be closed.
(G) Accessible valves in VOC service shall be monitored by leak-checking for fugitive emissions at least quarterly using an approved gas analyzer. For valves equipped with rupture discs, a pressure gauge shall be installed between the relief valve and rupture disc to monitor disc integrity. All leaking discs shall be replaced at the earliest opportunity, but no later than the next process shutdown. Sealless/leakless valves (including, but not limited to, welded bonnet bellows and diaphragm valves) and relief valves equipped with a rupture disc or venting to a control device are exempt from monitoring.
(H) Dual pump seals with barrier fluid at higher pressure than process pressure, seals degassing to vent control systems kept in good working order or seals equipped with an automatic seal failure detection and alarm system, submerged pumps, or sealless pumps (including, but not limited to, diaphragm, canned, or magnetic driven pumps) are exempt from monitoring.
(I) All other pump and compressor seals emitting VOC shall be monitored with an approved gas analyzer at least quarterly.
(J) After completion of the required quarterly inspections for a period of at least two years, the operator of the oil and gas facility may request in writing to the Office of Permitting, Remediation, and Registration that the monitoring schedule be revised based on the percent of valves leaking. The percent of valves leaking shall be determined by dividing the sum of valves leaking during current monitoring and valves for which repair has been delayed by the total number of valves subject to the requirements. This request shall include all data that has been developed to justify the following modifications in the monitoring schedule.
(i) After two consecutive quarterly leak detection periods with the percent of valves leaking equal to or less than 2.0%, an owner or operator may begin to skip one of the quarterly leak detection periods for the valves in gas/vapor and light liquid service.
(ii) After five consecutive quarterly leak detection periods with the percent of valves leaking equal to or less than 2.0%, an owner or operator may begin to skip three of the quarterly leak detection periods for the valves in gas/vapor and light liquid service.
(K) A directed maintenance program shall be used and consist of the repair and maintenance of VOC fugitive emission components assisted simultaneously by the use of an approved gas analyzer such that a minimum concentration of leaking VOC is obtained for each component being maintained. Replaced components shall be remonitored within 30 days of being placed back into VOC service.
(3) For owners and operators who are subject to the applicable parts of subsection (a)(11) of this section, auditory and visual checks for SO2 and H2 S leaks within the operating area shall be made every day. Immediately, but no later than eight hours upon detection of a leak, operating personnel shall take the following actions:
(A) isolate the leak; and
(B) commence repair or replacement of the leaking component; or
(C) use a leak collection/containment system to prevent the leak until repair or replacement can be made if immediate repair is not possible.
(d) Approved test methods.
(1) An approved gas analyzer used for the VOC fugitive inspection and repair requirement in subsection (c) of this section, shall conform to requirements listed in 40 CFR §60.485(a) and (b).
(2) Tutweiler analysis or equivalent shall be used to determine the H2 S content as required under subsections (a) and (e) of this section.
(3) Proper operation of any condenser used as a VOC emissions control device to comply with subsection (a)(5) of this section shall be tested to demonstrate compliance with the minimum control efficiency. Sampling shall occur within 60 days after start-up of new or modified facilities. The permittee shall contact the Engineering Services Section, Office of Compliance and Enforcement 45 days prior to sampling for approval of sampling protocol. The appropriate regional office in the region where the source is located shall also be contacted 45 days prior to sampling to provide them the opportunity to view the sampling. Neither the regional office nor the Engineering Services Section, Office of Compliance and Enforcement personnel are required to view the testing. Sampling reports which comply with the provisions of the "TNRCC Sampling Procedures Manual," Chapter 14 ("Contents of Sampling Reports," dated January 1983 and revised July 1985), shall be distributed to the appropriate regional office, any local programs, and the Engineering Services Section, Office of Compliance and Enforcement.
(e) Monitoring and recordkeeping requirements.
(1) If the operator elects to install and maintain ambient H2 S property line monitors to comply with subsection (a)(11) of this section, the monitors shall be approved by the Engineering Services Section, Office of Compliance and Enforcement office in Austin, and shall be capable of detecting and alarming at H2 S concentrations of ten ppmv. Operations personnel shall perform an initial on-site inspection of the facility within 24 hours of initial alarm and take corrective actions as listed in subsection (c)(3)(A) - (C) of this section within eight hours of detection of a leak.
(2) The results of the VOC leak detection and repair requirements shall be made available to the executive director or any air pollution control agency having jurisdiction upon request. Records, for all components, shall include:
(A) appropriate dates;
(B) test methods;
(C) instrument readings;
(D) repair results; and
(E) corrective actions. Records of flange inspections are not required unless a leak is detected.
(3) Records for repairs and replacements made due to inspections of H2 S and SO2 components shall be maintained.
(4) Records shall be kept for each production, processing, and pipeline tank battery or for each storage tank if not located at a tank battery, on a monthly basis, as follows:
(A) tank battery identification or storage tank identification, if not located at a tank battery;
(B) compound stored;
(C) monthly throughput in barrels/month; and
(D) cumulative annual throughput, barrels/year.
(5) A plan shall be submitted to show how ongoing compliance will be demonstrated for the efficiency requirements listed in subsection (b)(1)(D) of this section. The demonstration may include, but is not limited to, monitoring flowrates, temperatures, or other operating parameters.
(6) Records shall be kept on at least a monthly basis of all production facility flow rates (in standard cubic feet per day) and total sulfur content of process vents or flares or gas processing streams. Total sulfur shall be calculated in long tons per day.
(7) Records shall be kept of all ambient property line monitor alarms and shall include the date, time, duration, and cause of alarm, date and time of initial on-site inspection, and date and time of corrective actions taken.
(8) All required records shall be made available to representatives of the agency, the EPA, or local air pollution control agencies upon request and be kept for at least two years. All required records shall be kept at the plant site, unless the plant site is unmanned during business hours. For plant sites ordinarily unmanned during business hours, the records shall be maintained at the nearest office in the state having day-to-day operations control of the plant site.

30 Tex. Admin. Code § 116.620

The provisions of this §116.620 adopted to be effective April 19, 1996, 21 TexReg 3192; amended to be effective July 8, 1998, 23 TexReg 6973; amended to be effective September 4, 2000, 25 TexReg 8668