26 Tex. Admin. Code § 554.320

Current through Reg. 49, No. 25; June 21, 2024
Section 554.320 - Lighting and Illumination

Current recommendations of the Illumination Engineering Society of North America must be followed to achieve proper illumination characteristics and lighting levels throughout the facility. Minimum illumination must be ten foot candles in resident rooms and 20 foot candles in corridors, nurses stations, dining rooms, lobbies, toilets, bathing facilities, laundries, stairways, and elevators. Illumination requirements for these areas apply to lighting throughout the space and should be measured at approximately 30 inches above the floor anywhere in the room. Minimum illumination for overbed reading lamps, medication preparation or storage areas, kitchens, and nurse's station desks must be 50 foot candles. Illumination requirements for these areas apply to the task performed and should be measured on the task.

26 Tex. Admin. Code § 554.320

The provisions of this §19.320 adopted to be effective July 1, 1996, 21 TexReg 4408; Entire chapter transferred from Title 40, Pt. 1, Ch. 19 by Texas Register, Volume 45, Number 50, December 11, 2020, TexReg 8871, eff. 1/15/2021.