26 Tex. Admin. Code § 554.316

Current through Reg. 49, No. 25; June 21, 2024
Section 554.316 - Subdivision of Building Spaces-Smoke Barriers
(a) Subdivision of building spaces must be as required by NFPA 101.
(b) The facility must maintain the integrity of smoke barrier walls, including those parts of walls in attics and other concealed spaces.
(c) The facility must maintain the integrity of smoke dampers in air ducts.
(d) Ducts with smoke dampers must have maintenance panels for inspection. The maintenance panels must be removable without tools. Means of access must also be provided in the ceiling or side wall to facilitate smoke damper inspection readily and without obstruction. Location of dampers must be identified on the wall or ceiling of the occupied area below.

26 Tex. Admin. Code § 554.316

The provisions of this §19.316 adopted to be effective July 1, 1996, 21 TexReg 4408; Entire chapter transferred from Title 40, Pt. 1, Ch. 19 by Texas Register, Volume 45, Number 50, December 11, 2020, TexReg 8871, eff. 1/15/2021; Amended by Texas Register, Volume 46, Number 52, December 24, 2021, TexReg 9039, eff. 1/2/2022