26 Tex. Admin. Code § 553.123

Current through Reg. 49, No. 24; June 14, 2024
Section 553.123 - Means of Escape Requirements for an Existing Small Type B Assisted Living Facility
(a) The provisions of NFPA 101, Chapter 7, Means of Egress, do not apply to an existing small Type B assisted living facility, unless explicitly referenced by this section or by NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies.
(b) An existing small Type B assisted living facility must meet the requirements of 33.2.2, Means of Escape, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies, except as described in this section.
(c) An existing small Type B assisted living facility must ensure doors meet the requirements of 33.2.2.5, Doors, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies, and the additional requirements of this section. A resident room door is not otherwise required to meet the requirements for doors in 33.2.3.6, Construction of Corridor Walls, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies.
(1) A resident room door in an existing small Type B assisted living facility must latch in its frame to resist the passage of smoke.
(2) In an existing small Type B assisted living facility comprised of buildings that contain living units with independent cooking equipment within the living unit, a door between the living unit and a corridor or hallway must:
(A) be self-closing or automatic-closing; and
(B) latch in its frame to resist the passage of smoke.
(3) A resident room door or living unit door must not be arranged to prevent the occupant from closing the door.
(d) An existing small Type B assisted living facility providing spaces for use by residents on floors other than the ground floor must provide at least two separate approved stairs.
(1) An existing stair may be continued in service, subject to approval by HHSC.
(2) A stair used as means of escape must meet the requirements of 33.2.2.6, Stairs, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies.
(3) Each stair must be arranged and located so that it is not necessary to go through another room, including a bedroom or bathroom, to reach the stair.
(4) Each stair must be provided with handrails.
(5) Each stair must be provided with normal lighting according to the requirements of §553.128 of this division (relating to Electrical Requirements for an Existing Small Type B Assisted Living Facility).
(6) A stair in an existing building that became an assisted living through conversion must meet the dimensional criteria for existing stairs in 7.2.2.2, Dimensional Criteria, in NFPA 101, Chapter 7, Means of Egress.
(7) An existing stair, previously approved by HHSC, may be rebuilt to the same dimensions but must meet all other requirements for stairs in NFPA 101.

26 Tex. Admin. Code § 553.123

The provisions of this §553.123 adopted to be effective May 1, 1995, 20 TexReg 2629; amended to be effective August 1, 2000, 25 TexReg 6361; amended to be effective September 1, 2010, 35 TexReg 4471; transferred from Title 40, Chapter 92 by Texas Register, Volume 44, Number 15, April 12, 2019, TexReg 1886, eff. 5/1/2019; repealed by Texas Register, Volume 46, Number 33, August 13, 2021, TexReg 5020, eff. 8/31/2021; adopted by Texas Register, Volume 46, Number 34, August 20, 2021, TexReg 5189, eff. 8/31/2021