Equipment for automatic in-tank monitoring that tests for the loss of product and conducts automatic inventory reconciliation may be used as a release detection method if the automatic product level monitor test is conducted at least once every 30 days and the test is capable of detecting 0.2 gallon per hour leak rate with a probability of detection of 0.95 and a probability of false alarm of 0.05 and if automatic inventory reconciliation or another test of equivalent performance is conducted in accordance with the requirements for inventory reconciliation in subdivision 74:56:01:26(2).
S.D. Admin. R. 74:56:01:29
General Authority: SDCL 34A-2-93, 34A-2-99.
Law Implemented: SDCL 34A-2-98, 34A-2-99.