S.D. Admin. R. 74:53:01:26

Current through Register Vol. 51, page 64, December 9, 2024
Section 74:53:01:26 - Requirements for holding tanks

The requirements for holding tanks are as follows:

(1) The minimum liquid holding capacity shall be 1,000 gallons or the wastewater flow generated over a period of 7 days, whichever is greater. There shall be no discharge of effluent from the tank;
(2) The tank shall be equipped with a high-water alarm positioned to allow at least 3 days of storage after the alarm is activated;
(3) Holding tanks shall conform to the requirements for septic tanks under subdivisions 74:53:01:23(1) to (3), inclusive, with the exception of outlet devices; and
(4) Holding tanks shall be installed to meet the requirements for septic tanks under § 74:53:01:24.

S.D. Admin. R. 74:53:01:26

12 SDR 2, effective 7/18/1985; 13 SDR 129, 13 SDR 141, effective 7/1/1987; transferred from

General Authority: SDCL 34A-2-93.

Law Implemented: SDCL 34A-2-20.