S.D. Admin. R. 74:36:07:119

Current through Register Vol. 51, page 56, November 4, 2024
Section 74:36:07:119 - Existing municipal solid waste landfill non-enclosed flare monitoring

The owner or operator of an existing municipal solid waste landfill that seeks to comply with § 74:36:07:109 using a non-enclosed flare shall install, calibrate, maintain, and operate according to the manufacturers specifications, the following equipment:

1. A heat sensing device at the pilot light or the flame itself to indicate the continuous presence of a flame; and
2. A device that records flow to the flare and bypass of the flare, if applicable, at least every 15 minutes. The owner or operator shall secure the bypass line valve in the closed position with a car-seal or a lock-and-key type configuration. A visual inspection of the seal or closure mechanism shall be performed at least once every month to ensure the valve is maintained in the closed position and the gas flow is not diverted through the bypass line.

S.D. Admin. R. 74:36:07:119

46 SDR 064, effective 11/25/2019

General Authority: SDCL 34A-1-6.

Law Implemented: SDCL 34A-1-18.