Section 44:76:12:17 - Emergency electrical circuit connections Emergency electrical service shall be furnished to circuits as follows:
(1) Lighting of exit ways and all necessary ways of approach to them, including exit signs and exit direction signs, exterior of exits, exit doorways, stairways, and corridors;(2) Surgical room operating lights;(3) Lighting for laboratory, recovery room, staff stations, and medication preparation areas;(4) Lighting for the generator set location, the switch gear location, and the boiler room;(5) Equipment essential to life safety and for protection of important equipment or vital materials;(6) Staff calling system;(7) Alarm system, including fire alarms actuated at manual stations;(8) Water flow alarm devices of sprinkler system if electrically operated;(9) Fire detecting and smoke detecting systems;(10) Paging or speaker systems if intended for issuing instructions during emergency conditions;(11) Alarms required for nonflammable medical gas systems, if installed;(12) Pump for central suction system;(13) Sewage or sump lift pump, if installed;(14) Receptacles for blood bank refrigerator;(15) At least two duplex receptacles for the laboratory;(16) Receptacles in operating and recovery rooms except those for X ray;(17) Duplex receptacles in patient corridors; and(18) Equipment, such as burners and pumps, necessary for operation of one or more boilers required for heating and sterilization and their necessary auxiliaries and controls.S.D. Admin. R. 44:76:12:17