S.D. Admin. R. 20:45:05:16

Current through Register Vol. 50, page 162, June 24, 2024
Section 20:45:05:16 - Fire safety requirements for crematories attached to funeral establishments

A crematory which is a part of a funeral establishment or is physically attached to a funeral establishment must be separated from the funeral establishment by construction using noncombustible materials with a fire resistance rating of no less than two hours. As an alternative to a two-hour fire separation, an automatic sprinkler system may be installed in the funeral establishment and a one-hour fire separation constructed between the funeral establishment and the crematory.

S.D. Admin. R. 20:45:05:16

15 SDR 146, effective 4/2/1989; transferred from

General Authority: SDCL 34-26A-33.

Law Implemented: SDCL 34-26A-3, 34-26A-33.

The amended version of this section by 50 SDR 157, effective 7/2/2024 is not yet available.