S.D. Admin. R. 20:44:24:03

Current through Register Vol. 50, page 162, June 24, 2024
Section 20:44:24:03 - Additional requirements for temporary installations for carnivals and celebrations

In addition to the requirements of § 20:44:24:02, temporary installations for carnivals and celebrations must conform to the following:

(1) Each ride or concession must be provided with only one disconnect switch with overcurrent protection;
(2) Splices and taps must be enclosed in a weatherproof box or cabinet and may not be accessible to the public. Splices or taps may not be buried in the ground;
(3) Cable must be in good condition, have standard insulating qualities for the voltage level, have adequate mechanical strength, and be a continuous length from box to box. Outdoor cord connectors must be used;
(4) All temporary installations must be approved by the electrical inspector before use; and
(5) All installations must comply with SDCL chapter 36-16 and all provisions of this article.

S.D. Admin. R. 20:44:24:03

SL 1975, ch 16, § 1; 12 SDR 92, effective 1/1/1986; 12 SDR 151, 12 SDR 155, effective 7/1/1986; 18 SDR 83, effective 11/10/1991; 20 SDR 222, effective 7/6/1994; transferred from § 20:44:09:03, August 12, 1944.

General Authority: SDCL 36-16-12.

Law Implemented: SDCL 36-16-12, 36-16-27.