S.D. Admin. R. 20:44:22:27

Current through Register Vol. 50, page 162, June 24, 2024
Section 20:44:22:27 - Residential housing units moved to new locations

Single, modular, or multifamily residential units moved from one location to another must have at least a 100-ampere service at the new location and must meet the ground fault circuit interrupter protection, tamper resistant receptacle protection, arc-fault circuit interrupter protection, receptacle for heating and cooling equipment, weather resistant receptacles and in use cover, and emergency disconnect requirements of the National Electrical Code, Article:

(1) 210.8 - ground fault circuit interrupter protection;
(2) 210.12 - arc fault circuit interrupt protection;
(3) 406.12 - tamper resistant receptacles;
(4) 210.63 - receptacle within 25 feet of the heating and ac equipment;
(5) 406.9 . weather resistant receptacles and in use covers; and
(6) 230.85 . emergency disconnects.

S.D. Admin. R. 20:44:22:27

19 SDR 155, effective 4/14/1993; 20 SDR 222, effective 7/6/1994; transferred from; 43 SDR 181, effective 7/10/2017; 48 SDR 023, effective 9/15/2021

General Authority: SDCL 36-16-12.

Law Implemented: SDCL 36-16-27.