S.D. Admin. R. 20:44:22:25

Current through Register Vol. 50, page 162, June 24, 2024
Section 20:44:22:25 - Electrical receptacles in health care facilities

Patient care space in health care facilities, as defined in Article 517 of the National Electrical Code, must have receptacles listed for hospital use in other than hazardous locations. Such receptacles are identified by the marking "Hospital Only" or by the marking "Hospital Grade" and a green dot on the receptacle. The green dot must be visible after installation.

S.D. Admin. R. 20:44:22:25

19 SDR 155, effective 4/14/1993; transferred from

General Authority: SDCL 36-16-12.

Law Implemented: SDCL 36-16-12.