Section 61-93.2400.2401 - Receptacles (II)A. Patient Room. Each Patient room shall have duplex grounding type receptacles located to include one (1) at the head of each bed.B. Corridors. Duplex receptacles for general use shall be installed approximately fifty (50) feet apart in all corridors and within twenty-five (25) feet of the ends of corridors.S.C. Code Regs. § 61-93.2400.2401
Added by State Register Volume 44, Issue No. 06, eff. 6/26/2020.